首页> 外文会议>International Conference on Power Systems >Effect of Tower Footing Resistance on Back Flashover for A Double Circuit Line
【24h】

Effect of Tower Footing Resistance on Back Flashover for A Double Circuit Line

机译:塔架基础电阻对双回线反向闪络的影响

获取原文

摘要

An investigation is carried out on an EMTP model of a 400kV double circuit line to analyze overvoltages that occur due to a lightning strike on the phase and the ground wire. Lightning strike response corresponding to different front time and the tower footing resistance are analyzed. In this paper, the impact of back-flashover on the overvoltage profile at different points on the tower is also analyzed. It is observed that both tower footing resistance and front-time of lightning surge play a significant role in determining the value of over-voltage.
机译:对400kV双回路线的EMTP模型进行了研究,以分析由于相和地线上的雷击而产生的过电压。分析了与不同的前置时间相对应的雷击响应以及塔的基础阻力。在本文中,还分析了反闪对塔上不同点的过电压曲线的影响。可以看出,塔底电阻和雷电浪涌的前沿时间在确定过电压值方面都起着重要作用。