首页> 外文会议>International Conference on Condition Assessment Techniques in Electrical Systems >Detection of PD Activities in XLPE Cable Using UHF Antennas
【24h】

Detection of PD Activities in XLPE Cable Using UHF Antennas

机译:使用UHF天线检测XLPE电缆中的PD活性

获取原文

摘要

Underground cables are widely used in urban areas for electrical power transfer, and some of those cables are very old. These cable insulations are often subjected to partial discharges due to aging which, gradually degrades dielectric strength of the insulation and ultimately results in complete failure. Therefore, detection of partial discharge (PD) within the insulation of cross-linked polyethylene (XLPE) cable may help to get an early warning about the fault condition. This paper reports about initial results obtained from the measurement of PD activities within XLPE cable using standard electrical method and UHF method.
机译:地下电缆在城市地区广泛用于电力传输,其中一些电缆很旧。这些电缆绝缘层经常会因老化而发生局部放电,这会逐渐降低绝缘层的绝缘强度,并最终导致完全失效。因此,检测交联聚乙烯(XLPE)电缆绝缘层内的局部放电(PD)可能有助于获得有关故障状况的早期警告。本文报告了通过使用标准电学方法和UHF方法测量XLPE电缆中的PD活性而获得的初步结果。