摘要

Two-phase ground short circuit occurred on 35kV side of main transformer in a 220 kV substation. The low voltage side 301 circuit breaker did not jump off. Then the differential protection of the main transformer is started, which causes tripping of the three sides of the main transformer and no load loss. In this paper, the primary equipment, secondary equipment and monitoring background information related to the fault are investigated and analyzed in detail, and the causes and development process of the fault are restored. Because of the special fault, in order to avoid the similar situation happening again, some suggestions are put forward for the improvement of the merged intelligent device.
机译:220 kV变电站主变压器35 kV侧发生两相接地短路。低压侧301断路器未跳开。然后启动主变压器的差动保护,这将导致主变压器的三侧跳闸,并且没有负载损失。本文详细分析了与故障有关的一次设备,二次设备和监控背景信息,并恢复了故障的原因和发展过程。由于特殊的故障,为避免再次发生类似情况,为合并智能设备的改进提出了一些建议。