首页> 外文会议>International Conference on Lightning Protection >Achievements in the Measurement of Tower-footing Impulse Impedance of Transmission Lines
【24h】

Achievements in the Measurement of Tower-footing Impulse Impedance of Transmission Lines

机译:输电线路塔底脉冲阻抗的测量成果

获取原文

摘要

This paper presents results obtained from field measurements of tower-footing impulse impedance carried out in real transmission lines. Tests were performed using an impulsive voltage generator, measuring the ground potential rise and the impressed current to determine the impulsive grounding impedance. The results of the harmonic impedance measured for the same towers with a 25-kHz instrument showed to be consistent with the 25-kHz impedance derived from the impulsive GPR and current waveforms by applying FFT.
机译:本文介绍了在实际传输线中对塔底脉冲阻抗进行现场测量获得的结果。使用脉冲电压发生器进行测试,测量接地电位的上升和施加的电流,以确定脉冲接地阻抗。使用25 kHz仪器在同一塔上测得的谐波阻抗结果表明,与通过应用FFT从脉冲GPR和电流波形得出的25 kHz阻抗一致。