首页> 外文会议>International Conference on Lightning Protection >Study of Lightning Performance of 400 kV Transmission Line Interconnecting Poland and Lithuania (LitPol) in Years 2016 - 2017
【24h】

Study of Lightning Performance of 400 kV Transmission Line Interconnecting Poland and Lithuania (LitPol) in Years 2016 - 2017

机译:波兰和立陶宛(LitPol)互连的400 kV输电线路在2016年至2017年的防雷性能研究

获取原文

摘要

In the paper are described main features of lightning performance of 400 kV transmission line located in north-east part Poland and south-west Lithuania named LitPol Link. This line is a part of Baltic Ring - EU power grid project interconnecting transmission lines in seven countries surrounding the Baltic Sea. Some features of the line have special influence on lightning hazard mainly due to height of towers which vary from 40 to 97 m. The lightning activity in the region is based on the lightning location system LINET data. Recorded lightning CG discharges were correlated with individual outages of LitPol Link recorded by Polish operator of the line in years 2016-17. Exemplary outages were described in detail and some conclusions are presented.
机译:本文介绍了位于波兰东北部和西南立陶宛的名为LitPol Link的400 kV输电线路的雷电性能的主要特征。这条线路是波罗的海环网(Baltic Ring)的一部分,这是欧盟电网项目,将波罗的海周围七个国家的输电线路互连。线路的某些特征对雷电危害有特殊影响,这主要是由于塔高在40到97 m之间变化。该区域的闪电活动基于闪电定位系统LINET数据。记录的闪电CG放电与该行的波兰运营商在2016-17年记录的LitPol Link个别停机相关。详细描述了示例性中断,并给出了一些结论。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号