首页> 外文会议>Chinese Control and Decision Conference >Interconnection switch on-off state identification of distribution networks based on load measurement
【24h】

Interconnection switch on-off state identification of distribution networks based on load measurement

机译:基于负荷测量的配电网互联开关通断状态识别

获取原文

摘要

In this paper, two approaches of interconnection switch on-off state identification of medium voltage distribution network are proposed; one is using weighted least squares (WLS) to estimate the voltage variables of all nodes by measured values of end nodes under given possible topology models, and then using recursive Bayesian approach (RBA) to justify which topology model is the correct one; the second approach is using back-forward sweep (BFS) power flow algorithm to obtain the voltage variables of all nodes, then using the same RBP to identify the topology. The case study of IEEE 33 nodes distribution networks shows that both approaches have a high accuracy, but the BFS has a faster justification, fewer iterations, less computing time and simpler codes.
机译:提出了中压配电网互联开关通断状态识别的两种方法。一种是在给定的可能拓扑模型下,使用加权最小二乘(WLS)通过端节点的测量值来估计所有节点的电压变量,然后使用递归贝叶斯方法(RBA)来证明哪种拓扑模型是正确的;第二种方法是使用前向扫描(BFS)潮流算法获取所有节点的电压变量,然后使用相同的RBP来识别拓扑。 IEEE 33节点配电网络的案例研究表明,这两种方法均具有较高的准确性,但BFS具有更快的证明,更少的迭代,更少的计算时间和更简单的代码。