Effects of Overvoltage on Mesh-Distributed and Edge-Distributed Rods in Rectangular Ground Grid Systems of High Voltage Substations

机译:过电压对高压变电站矩形接地网中网格分布和边缘分布杆的影响

获取原文

摘要

In this study, the rectangular ground grids of the high voltage substations equipped with two different patterns of rods, including mesh-distributed and edge-distributed rods, were analyzed for the effects of overvoltage by using ATP/EMTP simulation program. By following the IEEE standard 80-2000, these two rectangular ground grids were designed to have the same area size of 324 square meters and then used for simulation by injecting the fault current of 25 kA at the center and corner of ground grids. The overvoltage occurred across the diagonal line and at the corner of these two rectangular ground grids were measured and compared with the calculated grid potential rise (GPR). The results showed that lower levels of overvoltage were found on mesh-distributed rods than on edge-distributed rods perhaps due to the possibility that overvoltage may disperse symmetrically on mesh-distributed rods and resulting in quickly distribution of overvoltage to ground soil. The results from this study can be useful for future designing of the ground grid systems of high voltage substations.
机译:在这项研究中,使用ATP / EMTP模拟程序分析了配备有两种不同类型的棒(包括网格分布棒和边缘分布棒)的高压变电站的矩形接地网对过电压的影响。通过遵循IEEE标准80-2000,将这两个矩形接地网格设计为具有324平方米的相同面积,然后通过在接地网格的中心和角落注入25 kA的故障电流来进行仿真。测量在对角线上和这两个矩形接地格栅的拐角处发生的过电压,并将其与计算出的电网电位上升(GPR)进行比较。结果表明,网状分布的杆比边缘分布的杆发现的过电压水平更低,这可能是由于过电压可能对称地分散在网状分布的杆上并导致过电压快速分布到地面土壤的可能性。这项研究的结果对于将来设计高压变电站的接地网系统很有用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号