Partial Non-Zero Fault Response of Grid-Connected DFIG

机译:并网DFIG的部分非零故障响应

获取原文

摘要

This paper presents a detailed experimental study of wind turbine DFIG response to non-zero grid faults that may occur at a considerable distance from the generator. An analytical solution of the generalized DFIG machine equations operating under non-zero fault conditions is developed in which the fault response is separated into three components: a natural response that describes zero voltage behavior, a component describing the retained voltage behavior and the forced response corresponding to the applied rotor voltage via the rotor-side power converter. The DFIG system fault response is examined experimentally using a 7.5kW test facility detailing example of a 500ms, 15% fault.
机译:本文介绍了风力发电机DFIG对可能在距发电机相当远的距离处发生的非零电网故障的响应的详细实验研究。开发了在非零故障条件下运行的广义DFIG机器方程的解析解,其中故障响应分为三个部分:描述零电压行为的自然响应,描述保留电压行为的组件和对应的强制响应通过转子侧功率转换器达到施加的转子电压。使用7.5kW测试设备对DFIG系统的故障响应进行了实验检查,详细说明了500ms,15%故障的示例。