In order to study the suppression effect of the overvoltage when the Impact capacitor is applied in the neutral bus of the High-voltage Converter station, this paper takes the BIN-JIN HVDC transmission project as the research object and establishes an internal overvoltage calculation model in the PSCAD/EMTDC. The variation of overvoltage amplitude in neutral bus which is in the ground short circuit fault and valve triggering pulse loss fault situation is calculated and analyzed under different impact capacitor configuration schemes. The calculation results showed: installing impact capacitor can significantly reduce the overvoltage level in the neutral Bus of the converter station; and the more the capacity of the impact capacitor increased, the more obvious the suppression effect is; The impact capacitor has a restraining effect on the overvoltage of the neutral bus only when it is on the same side with the bus. To sum up, the impact capacitor could be installed to reduce the level of the inner overvoltage.
机译:为了研究高压换流站中性母线上施加冲击电容器时过电压的抑制效果,以BIN-JIN高压直流输电工程为研究对象,建立了高压换流站内部过电压计算模型。 PSCAD / EMTDC。计算并分析了在不同的冲击电容配置方案下,中性线母线在接地短路故障和阀门触发脉冲损失故障情况下过电压幅值的变化。计算结果表明:安装冲击电容器可以显着降低换流站中性母线的过电压水平;冲击电容器的容量增加得越多,抑制效果越明显。冲击电容器只有在中性线与母线在同一侧时,才对中性线的过电压产生抑制作用。综上所述,可以安装冲击电容器以降低内部过电压的水平。