首页> 外文会议>International Conference on Smart City and Systems Engineering >The Analysis and Research of the Stress Cone Dislocation of 110kv Prefabricated Cable Terminal
【24h】

The Analysis and Research of the Stress Cone Dislocation of 110kv Prefabricated Cable Terminal

机译:110kV预制电缆终端应力锥错位分析与研究

获取原文

摘要

Based on the a breakdown of 110kV type flexible prefabricated cable terminal, Fault cable terminal inspection and accident cause analysis are carried out, the discharge traces and the stress cone dislocation found during the disintegration of the cable terminal are analyzed in detail, using the finite element method of cable terminal of high voltage electrostatic field distribution and values of stress cone dislocation the simulation results obtained, When the cable terminal stress cone is dislocated, the electric field distortion is serious, and there is a severe partial discharge in the power frequency, and through analysis, it is concluded that the fabrication and installation of cable terminals is the fundamental cause of the stress cone dislocation.
机译:基于110kV型柔性预制电缆端子的故障情况,进行了故障电缆端子的检查和事故原因分析,利用有限元对电缆端子在解体过程中的放电轨迹和应力锥错位进行了详细分析。高压静电场分布的电缆端子法和应力锥错位值的模拟结果得到,当电缆端子应力锥错位时,电场畸变严重,工频中存在严重的局部放电,通过分析可以得出结论,电缆端子的制造和安装是应力锥错位的根本原因。