When fault occurs in hybrid transmission line, the complicated refraction and reflection effects may happen during the propagation of fault traveling wave, this can lead to the decrease of fault ranging accuracy. To increase the fault ranging accuracy, the traveling wave propagation characteristics of overhead line - submarine cable hybrid line are analyzed, and a double terminal traveling wave ranging method of overhead line - submarine cable hybrid line is proposed, so the detailed double terminal ranging result can be obtained by analyzing the initial result. PSCAD is utilized to establish the simulation model of 500kV overhead line-submarine cable hybrid line and the simulation is carried out. The simulation results show that the double terminal traveling wave ranging method of hybrid line which is proposed can be simple, convenient, accurate and reliable to determine the specific location of the fault point of overhead Line - submarine cable hybrid line.
机译:当混合传输线发生故障时,在故障行波传播过程中可能发生复杂的折射和反射效应,从而导致故障测距精度的降低。为了提高故障测距的准确性,分析了架空线-海底电缆混合线路的行波传播特性,提出了架空线-海底电缆混合线路的双端行波测距方法,从而可以给出详细的双端测距结果。通过分析初始结果获得。利用PSCAD建立500kV架空线-海底电缆混合线的仿真模型,并进行了仿真。仿真结果表明,提出的混合线路双端行波测距方法可以简便,方便,准确,可靠地确定架空线-海底电缆混合线路故障点的具体位置。