Power transformer demagnetization

机译:电力变压器退磁

获取原文

摘要

Switching operations and direct current applied during routine testing procedures of static winding resistance measurement leave residual magnetization in the core and/or fully saturate the core of the transformer. When a magnetized power transformer is energized, it will face extremely high magnetizing currents due to the non-linear phenomenon of core saturation. The high level of inrush currents generated upon energization may affect the internal winding geometry of the transformer and also trip harmonic protection devices in the system. This paper will discuss the demagnetization of the magnetic core of power and distribution transformers. Different algorithms are applied to a variety of transformer designs and the results are validated with excitation current measurements and Sweep Frequency Response Analysis (SFRA) tests. The knowledge acquired and the best practices suggested for transformer demagnetization are summarized for practical application in the field.
机译:在静态绕组电阻测量的常规测试过程中施加的开关操作和直流电会在铁芯中留下残留的磁化强度和/或使变压器的铁芯完全饱和。给磁化功率互感器通电时,由于铁心饱和的非线性现象,它将面临极高的磁化电流。通电时产生的大量浪涌电流可能会影响变压器的内部绕组几何形状,还会使系统中的谐波保护设备跳闸。本文将讨论电力变压器和配电变压器的磁芯去磁。将不同的算法应用于各种变压器设计,并通过励磁电流测量和扫频响应分析(SFRA)测试来验证结果。总结了所获得的知识和建议的变压器退磁最佳实践,以供在该领域的实际应用。