Monitoring of leakage current on HV surge arrester as pollution indicator of external insulation

机译:监控高压避雷器上的泄漏电流,作为外部绝缘的污染指标

获取原文

摘要

The pollution of external insulation of power equipment has a significant impact on the lifetime of electrical equipment. The paper is focused on the possibility of using monitoring leakage current through the external insulation of hv surge arresters as indicator of pollution. In the experiment the modified procedure for the preparation of the polluting layer was used. The leakage current on the surface of the external insulation of the hv surge arrester and the internal leakage current of the hv surge arrester was monitored. It was found, that the surface resistivity of a sample with polluting layer in wet conditions, decreased by almost two orders of magnitude. The experimental results show that monitoring of leakage current along the surface of the external insulation is a useful indicator of pollution. In addition, measurement of the leakage current on the surge arrester with pollution layer during wet weather can lead to significantly erroneous results.
机译:电力设备外部绝缘的污染对电气设备的寿命有重大影响。本文着重探讨了使用监视通过高压电涌放电器外部绝缘的泄漏电流作为污染指标的可能性。在实验中,使用了修改的程序来制备污染层。监测高压电涌放电器外部绝缘表面的泄漏电流和高压电涌放电器的内部泄漏电流。发现,在潮湿条件下具有污染层的样品的表面电阻率降低了几乎两个数量级。实验结果表明,监测沿外部绝缘层表面的泄漏电流是一种有用的污染指标。此外,在潮湿天气中对带有污染层的电涌放电器的泄漏电流进行测量可能会导致明显错误的结果。