首页> 外文会议>International Conference on Power Systems >A Non-iterative Three Phase Distribution System Power Flow Analysis
【24h】

A Non-iterative Three Phase Distribution System Power Flow Analysis

机译:非迭代三相分布系统电力流分析

获取原文

摘要

A novel non-iterative three phase power flow has been proposed in this paper for distribution systems. Due to high R/X ratio and unbalance in load of distribution systems, the linear DC power flow is not applicable as resistance can’t be neglected. Moreover, voltage magnitudes play vital role in distribution systems. So, the aim of this paper is to develop a linear power flow for unbalanced distribution system which takes into account of both resistance and voltage magnitude along with reactance and voltage angle unlike DC power flow. The proposed method is implemented and tested on 19-bus, and 25- bus unbalanced radial distribution systems and is bench marked against standard backward forward sweep power flow analysis. Though the method is developed for unbalanced radial distribution systems, it is still valid for weakly mesh connected system as well.
机译:本文提出了一种新的非迭代三相电流,用于分配系统。由于分配系统负载高的R / X比和不平衡,线性直流电流不适用,因为电阻不能被忽略。此外,电压大小在分配系统中起着重要作用。因此,本文的目的是为不平衡分配系统开发线性电流,这考虑了电阻和电压幅度以及电抗和电压角,与直流电流不同。该方法在19总线上实现和测试,25总线不平衡径向分配系统,并且是针对标准向前扫描功率流分析的台阶。虽然该方法是为不平衡径向分配系统开发的,但它也仍然适用于弱网状连接系统。