PDC measurement and analysis is one of widely used tool for reliable diagnosis of power transformer insulation. In different reported methods of analysis it is considered that polarization current is composed of the current due to dipole movement and conduction current. Similarly the depolarization current is assumed to be composed of relaxation of dipoles. However when the dc conduction effect is removed from polarization current it is found the resulting current is not similar to the measured depolarization current. This deviation in both the currents show the presence of nonlinearity in the system. This nonlinearity arises due to migration of trapped charges that reside at the interfacial region of oil-paper insulation. The present paper shows the effect of such free charge on some important performance parameters like paper moisture and zero of Transfer Function of Classical Debye Model.
机译:PDC测量和分析是用于可靠诊断电力变压器绝缘的广泛使用的工具之一。在报告的不同分析方法中,认为极化电流由偶极子运动和传导电流引起的电流组成。类似地,假定去极化电流由偶极子的弛豫组成。但是,当从极化电流中除去直流传导效应时,发现所得电流与测得的去极化电流不相似。两个电流中的这种偏差表明系统中存在非线性。这种非线性是由于滞留在油纸绝缘层界面区域的电荷迁移而产生的。本文展示了这种免费电荷对一些重要性能参数的影响,例如纸张水分和古典德拜模型的传递函数为零。