首页> 外文会议>International Conference on Condition Assessment Techniques in Electrical Systems >Understanding incipient discharge activity and breakdown characteristics of composite oil under AC and DC voltages
【24h】

Understanding incipient discharge activity and breakdown characteristics of composite oil under AC and DC voltages

机译:了解交流和直流电压下复合油的初期放电活性和击穿特性

获取原文

摘要

Corona inception voltage (CIV) and breakdown strength of the composite oil formed with mineral and ester oil increase when the percentage of ester oil in the composite oil is increased. Corona inception voltage is higher under negative DC voltage compared with AC and positive DC voltages. Also, the variation in the breakdown voltage of composite oil under AC and positive DC is nearly the same and negative DC voltage has higher breakdown strength. The viscosity of the composite oil increases with increase in the percentage of ester oil in the composite oil. FTIR analysis provides functional groups present in the composite oil. UHF signal formed during corona activity in composite oil is much similar to what is observed in mineral oil/ester oil. The dominant frequency content in UHF signal formed is at 0.9 GHz. Spectrum analyzer results indicate that intermittent discharges occur due to corona in composite oil under AC voltages and burst type discharges occur under DC voltages and the factor is more predominant under negative DC voltages.
机译:当酯油在复合油中的比例增加时,由矿物油和酯油形成的复合油的电晕起始电压(CIV)和击穿强度会增加。在负直流电压下,电晕起始电压高于交流和正直流电压。而且,复合油在交流和正直流下的击穿电压变化几乎相同,而负直流电压具有更高的击穿强度。复合油的粘度随着复合油中酯油的百分比的增加而增加。 FTIR分析提供了复合油中存在的官能团。复合油在电晕活动过程中形成的UHF信号与矿物油/酯油中观察到的信号非常相似。形成的UHF信号中的主要频率成分为0.9 GHz。频谱分析仪结果表明,在交流电压下,复合油中的电晕会导致间歇性放电,而在直流电压下会发生突发性放电,而在负直流电压下,该因素更为明显。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号