The uneven air gap between the inner cavity of the stator and rotor’s outer circle is one of the main vibration sources of large hydro-generator sets. Unbalanced magnetic tension between the stator and rotor forms a frequency-exciting disturbance force on the rotor and stator. In this paper, in order to explore the relationship between the uneven air gap and the magnetic field strength as well as electromagnetic stress, magnetic induction intensity of inner air-gap magnetic field of the generator and the stress on the rotor surface are analyzed for six working conditions of the hydroelectric generator, including centering and eccentricity of the rotor. The influence of the hydroelectric generator’s air gap change rotor pole stress is studied with finite element software based on the structure of the generator.
机译:定子和转子外圈的内腔之间的不均匀气隙是大型水力发电机组的主要振动源之一。定子和转子之间的不平衡磁力张力在转子和定子上形成频率激发扰动力。在本文中,为了探讨不均匀的气隙与磁场强度以及电磁应力,发电机的内部空气间隙磁场的磁感应强度以及转子表面上的应力进行了六个水力发电机的工作条件,包括转子的定心和偏心。基于发电机结构的有限元软件研究了水力发电机的气隙变化转子杆应力的影响。