Together with the rising share of renewable generation more and more modern inverters are installed in the electricity grid. Existing standards for the characterization of harmonic emissions turn out not be suitable anymore for future requirements; e.g. today's guidelines do not help to prevent detrimental phenomena like harmonic resonances in systems with high penetration of renewables. This paper starts with giving some theoretical considerations about the correlation between voltages, currents and impedances for a Thévenin equivalent description of an inverter-grid system. A new method of Thévenin modelling based on sets of independent measurements is presented. Finally the impedance-based stability criterion will be applied to a real measured resonance in a 44 MW PV power plant. In conclusion the paper discusses methods, which are suitable to get a better understanding of the harmonic behavior of inverters, which can help to avoid power quality problems in advance.
机译:随着可再生能源发电份额的增加,电网中安装了越来越多的现代逆变器。事实证明,现有的表征谐波发射的标准已不再适合将来的要求。例如如今的指南无助于防止有害现象,例如在具有高可再生能源渗透率的系统中的谐波共振。本文首先就Thévenin逆变器-电网系统等效描述中的电压,电流和阻抗之间的相关性给出一些理论上的考虑。提出了一种基于独立测量集的Thévenin建模的新方法。最后,基于阻抗的稳定性标准将应用于44兆瓦光伏电站中的实际测量谐振。总之,本文讨论了一些方法,这些方法适合于更好地理解逆变器的谐波特性,有助于提前避免电能质量问题。