首页> 外文会议>International Conference on Lightning Protection >A conductor arrangement that overcomes the effective length issue in transmission line grounding: full-scale measurements
【24h】

A conductor arrangement that overcomes the effective length issue in transmission line grounding: full-scale measurements

机译:一种导体布置,克服了传输线接地的有效长度问题:满量程测量

获取原文

摘要

Usually, for high resistivity soils, increasing the length of the grounding electrode does not lead to a reduction in the impedance values due to the effective length issue. In this work, an improvement in a previously proposed special arrangement, which overcomes the effective length problem, is numerically and experimentally evaluated. The transient voltage response of this new arrangement is calculated and measurements were performed on a full-scale grounding electrode arrangement. Simulation results and measurements are compared for validation purposes.
机译:通常,对于高电阻率的土壤,增加接地电极的长度不会导致由于有效长度问题导致阻抗值的降低。在这项工作中,在数值和实验评估了以前提出了先前提出的特殊安排的改进,其克服了有效长度问题。计算这种新布置的瞬态电压响应,并对全级接地电极布置进行测量。进行仿真结果和测量以进行验证目的。