首页> 外文会议>International Conference on Lightning Protection >Factors influencing the probability of an apparatus damage in an extended earthing arrangement
【24h】

Factors influencing the probability of an apparatus damage in an extended earthing arrangement

机译:在扩展接地布置中影响设备损坏可能性的因素

获取原文

摘要

In the present paper lightning overvoltages on apparatus bonded to an extended earth arrangement are investigated. A case study of a large earthing grid (200m × 200m) covering an industrial plant is considered where a stand-alone power supply system (no connection to external lines) is supplying apparatus powered by a secondary board, earthed to a different point from the main distribution board. The values of the stressing voltage on the apparatus due to resistive coupling, the protection measures to be adopted according to the different characteristics of the lines connecting the distribution boards, and the probability of apparatus failure are evaluated. The analysis, performed by several simulations by means of the transient software EMTP-RV, show that protection against lightning of structures and of industrial plant may require the adoption of technical solutions that, even if in accordance with standards [1-4], need a particular study.
机译:在本文中,研究了连接到扩展接地装置的设备上的雷电过电压。考虑一个覆盖工业厂房的大型接地网(200m×200m)的案例研究,其中一个独立的电源系统(不连接外部线路)为由次级板供电的设备供电,该次级板的接地点与设备的接地点不同。主配电板。评估了由于电阻耦合而引起的设备上的应力电压值,根据连接配电板的线路的不同特性而应采取的保护措施以及设备发生故障的可能性。通过瞬态软件EMTP-RV进行的多次仿真分析表明,针对建筑物和工业厂房的雷击防护可能需要采用即使根据标准[1-4]仍需要的技术解决方案。一项特殊的研究。