Field measurements, modeling, and analysis of power system harmonics caused by industrial customers

机译:现场测量,建模和电力系统谐波分析由工业客户造成的电力系统谐波

获取原文

摘要

Due to problems caused by non-linear loads in a power system, a harmonic technical analysis on the hydroelectric generating units Illuchi 1 and 2 of the Electric Utility Company of Cotopaxi Province ELEPCO S.A., Ecuador, is performed in this project by means of industrial analyzers as well as software simulation. The analysis starts from harmonic distortion measurements on the generating plants and El Calvario substation. Then, simulations are performed including non-linear loads characterized as current sources in the east zone of the studied system by using a harmonic power flow to determine the industrial load causing the current fluctuations. The maximum values of THD are in the order of 5.4% and 3% in Illuchi 1 and 2, respectively, that are above the recommended values of IEEE Std. 519-1992. Based on these results and determined the cause, filters for 5 and 7 harmonic according to the IEEE Std. 1531-2003 are designed.
机译:由于电力系统中的非线性负载引起的问题,通过工业分析仪在本项目中进行了对Cotopaxi省Elepco Sa的电气公用事业公司的水力发电单位1和2的谐波技术分析。以及软件模拟。分析从发电厂和EL Calvario变电站上的谐波失真测量开始。然后,通过使用谐波功率流来确定所表征为所研究系统的东部区域的电流源的非线性载荷来执行模拟,以确定导致电流波动的工业负荷。在Illuchi 1和2中,THD的最大值分别为5.4%和3%,高于IEEE STD的推荐值。 519-1992。基于这些结果并确定了根据IEEE STD的5和7次谐波的原因,滤波器。 1531-2003设计。