首页> 外文会议>IEEE Canadian Conference on Electrical and Computer Engineering >Impacts of distributed generation on the coordination of protective devices in distribution network
【24h】

Impacts of distributed generation on the coordination of protective devices in distribution network

机译:分布式发电对配电网中保护装置协调的影响

获取原文

摘要

The problems of selectivity and coordination of protection devices is one of the concerns related to the effects of the insertion of distributed sources. Those problems directly affect the safety of equipment and personnel and continuity of service. Analysis should be done to determine if the protective devices installed on the network are properly coordinated after inserting distributed sources. In the paper, the effects of the insertion of distributed sources in an electrical distribution system were evaluated and analyzed. A network with three distributed sources namely induction machine, wind turbine generator and synchronous machine was studied. Short circuit was performed on the different buses of the distribution network to determine its impacts on the short circuit currents and its detection time. The results show an increase in short circuit current on the nearest bus of the load (bus 3), while the detection time remains constant over the latter, but variable on the other two. These results are quite similar for the three studied cases and confirm perfectly those found in the literature.
机译:保护装置的选择性和协调性问题是与插入分布式电源的影响有关的关注点之一。这些问题直接影响设备和人员的安全以及服务的连续性。应该进行分析,以确定插入分布式电源后网络上安装的保护设备是否正确协调。在本文中,评估和分析了在配电系统中插入分布式电源的影响。研究了具有三个分布式电源的网络,即感应电机,风力发电机和同步电机。在配电网络的不同母线上进行短路以确定其对短路电流的影响及其检测时间。结果表明,负载的最近总线(总线3)上的短路电流增加,而负载的检测时间保持不变,而其他两个上的检测时间却有所变化。对于三个研究案例,这些结果是非常相似的,并且完全证实了文献中的发现。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号