首页> 外文会议>International Conference on Modelling, Identification and Control >Analytical study of grid connected DFIG based wind turbine under grid fault conditions
【24h】

Analytical study of grid connected DFIG based wind turbine under grid fault conditions

机译:电网故障条件下并网双馈风力发电机的分析研究

获取原文

摘要

Doubly-Fed Induction Generator (DFIG) has been widely used in variable-speed Wind Energy Conversion System (WECS). The aim of this paper is to present a comparative study in term of the dynamic performances between two classical controllers Proportional Integral (PI) and Integral Proportional (IP) to control a DFIG during grid faults, which are represented by a voltage dip on all three phases of the grid voltage. Firstly, we are developed the model mathematic of the generator. Then, we introduced the technical of stator-flux-oriented vector control to decouple the stator active and reactive powers to simulate the behaviour of the wind turbine generator during fault conditions. The results of simulations realized under Matlab/Simulink, are analyzed and interpreted to show the performances of each controller.
机译:双馈感应发电机(DFIG)已广泛用于变速风能转换系统(WECS)。本文的目的是就电网故障期间两个经典控制器比例积分(PI)和积分比例(IP)之间的动态性能进行比较研究,以控制DFIG,这三个参数均由三个方向上的电压跌落来表示。电网电压的相位。首先,我们开发了发电机的模型数学。然后,我们引入了面向定子磁通的矢量控制技术,以使定子有功功率和无功功率解耦,以模拟风力发电机在故障情况下的行为。对在Matlab / Simulink下实现的仿真结果进行了分析和解释,以显示每个控制器的性能。