首页> 外文会议>International Conference on Electrical Engineering and Informatics >Alternative method for testing overcurrent protection function by using least square method finding overcurrent function parameters without prior interrogation of relay setting
【24h】

Alternative method for testing overcurrent protection function by using least square method finding overcurrent function parameters without prior interrogation of relay setting

机译:使用最小二乘法发现过流函数参数的最小二乘法测试过电流保护功能的替代方法,而无需先前询问中继设置

获取原文

摘要

A utility usually installed modern power system protection relays from multiple manufacturers and models. The testing of the relays is very challenging due to its complexity. This would increase expenses due to additional test duration and longer disturbance of power for the substation can't be energized. Therefore a test that could be done without prior accessing the setting would be needed for faster on site test. In this study, the alternative test method and procedure for by passing the setting complexity was evaluated. The result of testing data of overcurrent protection function at optimum number of valid test points was processed to reveal the setting of the functions. The calculation provided the time multiplier setting, minimum pickup current and the curve of the setting. The result suggests a valid testing could be done without extracting preexisting function setting.
机译:实用程序通常从多个制造商和型号安装现代电力系统保护继电器。由于其复杂性,对继电器的测试非常具有挑战性。这将增加由于额外的测试持续时间而增加的费用,并且对变电站的功率较长的扰动不能通电。因此,在现场测试时,需要在没有先前访问设置的情况下进行的测试。在本研究中,评估了通过通过设置复杂度的替代测试方法和过程。处理在最佳数量的有效测试点上的过电流保护功能数据的结果,以显示功能的设置。该计算提供了时间乘数设置,最小拾取电流和设置的曲线。结果表明可以在不提取预先存在的函数设置的情况下进行有效测试。

著录项

相似文献