首页> 外文会议>IEEE International Symposium on Power Electronics for Distributed Generation Systems >Investigation into the post-fault recovery time of a droop controlled inverter-interfaced microgrid
【24h】

Investigation into the post-fault recovery time of a droop controlled inverter-interfaced microgrid

机译:下垂控制的逆变器接口微电网故障后恢复时间的研究

获取原文

摘要

A two inverter microgrid, where each inverter uses droop control to share the network load, was simulated to investigate the recovery time after the clearance of a fault. A simple microgrid of only two inverters was used to understand interactions between different parameters within the microgrid after a fault had been cleared. Upon successful verification, a more complex microgrid could be used to test the ideas developed. This paper presents the fault response and the settling time of the droop controllers when the line inductance, trip setting and inverter fault current were changed in simulation. Results showed that the recovery time of the microgrid was most sensitive to the line inductance and least sensitive to the trip current of the inverters. When the line inductance was small the recovery time was less sensitive and when the line inductance was large the recovery time more sensitive to fault duration and fault current.
机译:模拟了两个逆变器微电网,其中每个逆变器使用下垂控制来分担网络负载,以研究故障清除后的恢复时间。清除故障后,仅使用两个逆变器的简单微电网来了解微电网内不同参数之间的相互作用。成功验证后,可以使用更复杂的微电网来测试开发的想法。本文介绍了在仿真中改变线电感,跳闸设置和逆变器故障电流时,下垂控制器的故障响应和建立时间。结果表明,微电网的恢复时间对线路电感最敏感,对逆变器的跳闸电流最不敏感。当线路电感较小时,恢复时间对灵敏度的影响较小;而当线路电感较大时,恢复时间对故障持续时间和故障电流更为敏感。