首页> 外文会议>IEEE International Symposium on Power Electronics for Distributed Generation Systems >A DC noise error compensator of single-phase grid-connected converter in D-Q synchronous reference frame
【24h】

A DC noise error compensator of single-phase grid-connected converter in D-Q synchronous reference frame

机译:D-Q同步参考系中单相并网转换器的直流噪声误差补偿器

获取原文

摘要

This paper proposes a dc error compensation algorithm using d-q synchronous coordinate transform phase-locked-loop in single-phase grid-connected converters. The DC errors are caused by the process of analog to digital conversion and the distorted grid voltage. The DC error can be remove by controlled the synchronous d-axis voltage using integral operation and digital infinite impulse response filter. In this paper, integral compensator and digital infinite impulse response filter are applied in order to remove the DC errors which cause the periodic ripples with grid frequency in D-Q synchronous coordinate transform phase-locked-loop.
机译:提出了一种单相并网变换器中采用d-q同步坐标变换锁相环的直流误差补偿算法。直流误差是由模数转换过程和电网电压失真引起的。可以通过使用积分操作和数字无限脉冲响应滤波器控制同步d轴电压来消除DC误差。本文采用积分补偿器和数字无限冲激响应滤波器,以消除在D-Q同步坐标变换锁相环中引起电网频率周期性波动的直流误差。