首页> 外文会议>International Conference on Bioinformatics and Biomedical Engineering >The Performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit
【24h】

The Performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit

机译:热回收型热管间接蒸发冷却空调单元的性能试验与分析

获取原文

摘要

Combining the heat recovery technology of heat pipe and evaporative cooling technology, this article researched a heat recovery heat pipe-type indirect evaporative cooling air-conditioning unit and tested this unit. Based on analyzing we got main perfoprmance factors and best operation parameters. The best ratio of volume of secondary air and primary air is 0.8, the best water delivery is 0.322 m3/h, the efficiency of heat pipe-type indirect evaporative cooler is 70.39%.This research provided reliable reference for the research and development of air-conditioning unit.
机译:结合热管和蒸发冷却技术的热回收技术,本文研究了热回收热管式间接蒸发冷却空调单元并测试本机。基于分析,我们得到了主要的完善因素和最佳运行参数。二次空气和初级空气的最佳比例为0.8,最佳水递送为0.322m3 / h,热管式间接蒸发冷却器的效率为70.39%。本研究为空气的研究和开发提供了可靠的参考 - 监管单位。