The reignition characteristics of double vacuum interrupters in series after interrupting vacuum arcs

机译:中断真空电弧后串联的双重真空灭弧室的重燃特性

获取原文

摘要

Vacuum circuit breakers are extending their applications from low/medium voltage level to high voltage level due to their good properties. Multi-break vacuum circuit breakers are used in special applications because thry have better breaking capability and withstand higher breakdown voltage compared with single-break vacuum circuit breakers. The objective of this paper is to investigate the reignition characteristics of double VIs in series after interrupting vacuum arc. Two 24kV VIs, which have axial magnetic field contacts and can interrupt a rated short circuit current of 31.5kA, were connected in series. The experiments were carried out in the synthetic circuit providing transient recovery voltage (TRV) with a peak value of 85 kV and a interrupted current of 5 kA. The arcing time was 1ms corresponding to the contact gap 1.2mm. The TRV across VIs were measured by voltage dividers. The results showed that the upper VI was reignited at first due to its higher TRV caused by stray capacitances and then led to the reignition of the lower one. The breaking capability of the double VIs in series was determined by the dielectric recovery of the upper VI and the minimum recovery time was about 2μs.
机译:真空断路器由于其良好的性能,正在将其应用从低/中电压等级扩展到高电压等级。多断点真空断路器用于特殊应用中,因为与单断点真空断路器相比,它们具有更好的分断能力并能承受更高的击穿电压。本文的目的是研究在中断真空电弧后串联的双VI的重燃特性。串联连接了两个24kV VI,这些VI具有轴向磁场接触并可以中断31.5kA的额定短路电流。实验是在合成电路中进行的,该合成电路提供的瞬态恢复电压(TRV)的峰值为85 kV,中断电流为5 kA。电弧放电时间为1ms,对应于1.2mm的接触间隙。通过分压器测量VI上的TRV。结果表明,由于杂散电容引起的TRV较高,上层VI首先被重新点燃,然后导致下层VI的重新点燃。串联双VI的分断能力取决于上部VI的介电恢复,最短恢复时间约为2μs。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号