This paper develops a liquid cooled high efficiency three-phase current source rectifier (CSR) for data center power supplies based on 400 Vdc architecture, using SiC MOSFETs and Schottky diodes. The 98.54% efficiency is achieved at full load. The rectifiers are paralleled to achieve high power ratings and system redundancy. The current balance and hot-swap of paralleled CSRs are realized in simulation using master-slave control. Moreover, an improved modulation scheme through adjustment of the freewheeling state is proposed and verified to effectively suppress the circulating current.
展开▼
机译:本文开发了基于400 V DC INF>架构的数据中心电源的液体冷却的高效三相电流源整流器(CSR),使用SIC MOSFET和肖特基二极管。 98.54%的效率在满载时实现。 整流器并联以实现高功率额定值和系统冗余。 使用主从控制的仿真实现了并联CSR的当前平衡和热插拔。 此外,提出了通过调整续流状态的改进的调制方案,并验证以有效地抑制循环电流。
展开▼