All distributed generating units need to be equipped with an anti-islanding (AI) protection scheme in order to avoid unintentional islanding. Unfortunately most AI methods fail to detect islanding when the islanded load matches with the production in the island. Another concerning issue is that certain active AI protection schemes may cause power quality problems. This paper proposes an AI protection method which is based on the combination of a specially designed reactive power versus frequency (Q-f) droop, and a constantly injected reactive power variation (RPV) pulse. The method is designed so that the injection of reactive power is of minor scale during normal operating conditions. Yet, the method shows high performance during islanding. Simulations were performed with the help of PSCAD/EMTDC in order to analyze the performance of the method. The results indicate that the method is able to detect islanding within 2 seconds even in a perfectly balanced island.
机译:所有分布式发电机组都需要配备防孤岛(AI)保护方案,以避免意外的孤岛现象。不幸的是,当孤岛负载与孤岛中的产量匹配时,大多数AI方法都无法检测到孤岛。另一个令人担忧的问题是某些主动AI保护方案可能会导致电能质量问题。本文提出了一种AI保护方法,该方法基于专门设计的无功功率随频率(Q-f)下降和恒定注入的无功功率变化(RPV)脉冲的组合。该方法被设计成使得在正常操作条件下无功功率的注入较小。然而,该方法在孤岛期间显示出高性能。为了分析该方法的性能,在PSCAD / EMTDC的帮助下进行了仿真。结果表明,该方法即使在完美平衡的孤岛中也能够在2秒内检测到孤岛。