THE EFFECT OF FIRE SPREAD ON STEEL-CONCRETE FLOOR

机译:火灾蔓延对钢混凝土地板的影响

获取原文

摘要

The paper describes the impact of fire spread on the behaviour of the steel and concrete composite floor.The spatial and temporal evolution of the gas temperature calculated in NIST code FDS,which was validated to experimental measurements, is applied to the composite floor of dimensions 9.0 m by 9.0 m.Mechanical behaviour of the composite slab highly affected by regions of high temperatures and areas with only elevated temperatures is solved in code Vulcan.To highlight the severity of spreading fire causing non-uniform temperature conditions, which after-effects differ from traditional methods, a comparison of both methods is introduced.The calculation of mechanical behaviour of the composite floor is repeated in a serious of three different thermal loading cases.Results of all cases are then compared in terms of vertical displacement and axial force in several positions of the composite floor.
机译:本文描述了火势蔓延对钢和混凝土复合地板性能的影响。将NIST代码FDS计算的气体温度的时空演变(经实验测量验证)应用于尺寸为9.0的复合地板m by 9.0 m。代码Vulcan解决了受高温区域和仅高温区域高度影响的复合板的力学行为,着重指出了造成不均匀温度条件的蔓延火焰的严重性,其后效与传统方法中,将两种方法进行了比较。在三种不同的热载荷情况下,重复了复合地板的力学性能计算,然后比较了几种情况下在多个位置的垂直位移和轴向力的结果复合地板。