首页> 外文会议>International symposium on heating, ventilation and air conditioning >Analysis on Influence Factors of Lewis Number in a Crossflow Reversibly Used Cooling Tower by Experimental Investigation
【24h】

Analysis on Influence Factors of Lewis Number in a Crossflow Reversibly Used Cooling Tower by Experimental Investigation

机译:通过实验研究分析刘易斯数字在横流中的影响因素可逆使用冷却塔通过实验研究

获取原文

摘要

Reversibly used cooling towers (RUCT) are used to extract heat from atmospheric to water. In this study, the factors influencing the value of Lewis number in a RUCT are analyzed by experimental investigation. The results show that Lewis number increases with the increase of water-air flow rate ratio. When the water-air flow rate ratio is constant, the Lewis number decreases with the increase of inlet water temperature and inlet air wet-bulb temperature, increases with the increase of inlet air dry-bulb temperature and water sprinkle density. This research offers a fundamental basis for studying heat and mass transfer characteristics in a cross flow reversibly used cooling tower and practical application.
机译:可逆使用的冷却塔(渣)用于从大气中提取热量。在这项研究中,通过实验研究分析了影响轨迹中Lewis数量的因素。结果表明,刘易斯数随着流量流量比率的增加而增加。当水流量比率恒定时,随着入口水温和入口空气湿泡温度的增加,路易斯数量随着入口空气干燥泡温度和水洒密度的增加而增加。本研究为在交叉流动可逆使用的冷却塔和实际应用中研究了研究热量和传质特性的基础基础。