首页> 外文会议>International symposium on heating, ventilation and air conditioning >Analysis of Microbiology Test of Air-Conditioning System in Severe Cold Area
【24h】

Analysis of Microbiology Test of Air-Conditioning System in Severe Cold Area

机译:严寒地区空调系统微生物学测试分析

获取原文

摘要

Central air-conditioning system of Liaoning Provincial Museum has been taken as the target to study microbiology contamination since it is a typical public building. Three AHUs that conduct with different functional areas were considered as testing object in the museum, including constant temperature and humidity AHU B1, B2, and B3. Using microbiological method, six levels of impingement air microorganism sampler, fluorescent optical microscope, high-pressure steam sterilization pot, thermostatic incubator, thermostatic oven, biochemical incubator, and testing instruments are selected to test dust and air, which contain microbial organisms in the AHUs. Results show that the average product dust of the museum is 12.36 g/m~2; the dust contains bacterial concentration in the microbiological is 85.2 x 104 cfu/m~2, the air contains bacterial concentration in the microbiological is 568.19 cfu/m~3, and the fungus concentration is 938.37 cfu/m~3; the advantage strains in microbiologic is gram-positive bacterium; advantage strains in fungus is penicillium, aspergillums, branch spore mold.
机译:由于是典型的公共建筑,辽宁省博物馆的中央空调系统已成为研究微生物污染的目标。博物馆将三个在不同功能区域进行操作的AHU作为测试对象,包括恒温恒湿AHU B1,B2和B3。使用微生物学方法,选择了六级撞击空气微生物采样器,荧光光学显微镜,高压蒸汽灭菌锅,恒温培养箱,恒温烤箱,生化培养箱和测试仪器来测试粉尘和空气,这些粉尘和空气中的AHU中含有微生物。结果表明,该博物馆的平均产品粉尘为12.36 g / m〜2。微生物中的粉尘中细菌浓度为85.2×104cfu / m〜2,微生物中的空气中细菌浓度为568.19cfu / m〜3,真菌浓度为938.37cfu / m〜3。微生物学上的优势菌株是革兰氏阳性细菌。真菌的优势菌株是青霉,曲霉,分支孢子霉。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号