摘要

High voltage Gas Insulated Substation (GIS) is threatened by Very Fast Transient Overvoltage (VFTO) which is high amplitude and high frequency transient within the range from 100 kHz up to 50 MHz in power systems. Operation of Disconnecting Switch is the main origin of these overvoltage phenomena that is analyzed in this paper. In this study, the effects of several parameters that influence on VFTO amplitude have been discussed. The focus of this paper is on the VFTO study of "Siah-bishe" power plant 400kV GIS substation. The study was carried out by modeling all pieces of equipment in EMTP-RV and careful consideration of different modeling guidelines and instructions described in available standards.
机译:高压气体绝缘变电站(GIS)受到超快速瞬态过电压(VFTO)的威胁,该瞬态过电压在电力系统中的高幅值和高频瞬变范围为100 kHz至50 MHz。隔离开关的操作是这些过电压现象的主要根源,本文将对此进行分析。在这项研究中,已经讨论了影响VFTO幅度的几个参数的影响。本文的重点是“ Siah-bishe”电厂400kV GIS变电站的VFTO研究。通过在EMTP-RV中对所有设备建模,并仔细考虑可用标准中描述的不同建模指南和说明来进行研究。