首页> 外文会议>Annual Conference for Protective Relay Engineers >Negative-sequence overcurrent considerations for induction motor loads
【24h】

Negative-sequence overcurrent considerations for induction motor loads

机译:感应电动机负载的负序过电流考虑

获取原文

摘要

Negative-sequence overcurrent (51Q) elements can add sensitivity to transformer and feeder protection. Because these elements do not respond to balanced load current, they can be set below phase overcurrent elements. However, certain loads may cause higher than expected negative-sequence current to flow because their negative-sequence impedance is quite low when compared to their positive-sequence impedance. This paper describes an event in which a 51Q element operated for a fault on an adjacent feeder, discusses the impact of voltage unbalance on induction motors, and examines induction motor load modeling and sequence networks. The analysis is supported by a PSCAD model developed for this event. The paper also shares specific lessons learned to assist engineers to securely set 51Q elements in the presence of induction motor loads.
机译:负序过电流(51Q)元件可以为变压器和进料器保护添加敏感性。因为这些元素没有响应平衡负载电流,所以它们可以设置为低于相位过电元素。然而,某些负载可能导致高于预期的负序电流流量,因为与它们的正序阻抗相比,它们的负序阻抗非常低。本文介绍了一种事件,其中51Q元件在相邻馈线上运行的故障,讨论了电压不平衡对感应电机的影响,并检查了感应电动机负载建模和序列网络。该分析由为此事件开发的PSCAD模型支持。本文还分享了特定的经验教训,以帮助工程师在存在感应电动机负载的情况下安全地设置51Q元素。

著录项