首页> 外文会议>Annual Conference for Protective Relay Engineers >Rotor DC current measurement by using current transformers
【24h】

Rotor DC current measurement by using current transformers

机译:转子直流电流测量通过使用电流互感器

获取原文

摘要

Generator protection has traditionally only measured stator AC currents and voltages. Measurement of rotor DC current was typically more difficult and required special measurement equipment (e.g. resistive shunt) in the rotor DC circuit. With advance of numerical technology it is now actually feasible for modern Intelligent Electronic Devises (i.e. IEDs) to measure the rotor winding DC current by utilizing standard CTs installed on the excitation transformer which feeds the static exciter (see Figure 1). By utilizing the measured AC currents from this CT the rotor DC current can be accurately measured by the IED. This can improve generator protection in several ways. Also useful information about excitation system behavior can be obtained from such measurements. Theoretical background and actual site measurements in a trail installation on a 315MVA, 11kV synchronous machine in a pump-storage hydro power plant will be presented in this paper.
机译:发电机保护传统上仅测量定子AC电流和电压。转子DC电流的测量通常更困难,并且在转子DC电路中的特殊测量设备(例如电阻分流)更加困难和所需的特殊测量设备(例如电阻分流)。随着数值技术的推进,它现在可以通过利用安装在静电激励器的激励变压器上的标准CTS来测量转子绕组DC电流来测量转子绕组直流电流的可行性(参见图1)。通过利用该CT的测量的AC电流,可以通过IED精确地测量转子DC电流。这可以通过几种方式改善发电机保护。还可以从这些测量中获得有关激励系统行为的有用信息。本文将介绍315MVA,11kV同步机上的315MVA上安装的理论背景和实际站点测量,将在泵送储存水电站中展示。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号