首页> 外文会议>Annual Conference of the IEEE Industrial Electronics Society >Suppression of arc grounding overvoltage by using ZnO nonlinear resistance grounding mode
【24h】

Suppression of arc grounding overvoltage by using ZnO nonlinear resistance grounding mode

机译:ZnO非线性电阻接地模式抑制电弧接地过电压

获取原文

摘要

Developments in power capacity have made arc grounding overvoltage increasingly prominent. This paper proposes a new method for determining current-voltage (I-V) characteristics of ZnO nonlinear resistance on a new grounding mode, by analyzing the power system through the symmetrical component method, considering system capacities, operation mode, and other characteristics. Then, the I-V characteristics of ZnO nonlinear resistance are obtained through the segmental linearization method. Finally, a model based on an actual 10kV system is established, and the different grounding modes are compared and simulated by ATP-EMTP. Results indicate that the designed ZnO nonlinear resistance parameters can suppress arc grounding overvoltage, and the proposed grounding mode is safe and reliable.
机译:电力容量的发展使电弧接地过电压越来越突出。本文通过对称分量方法分析电力系统,考虑系统容量,操作模式等特征,提出了一种确定新的接地模式对新接地模式的电流电压(I-V)特性的新方法。然后,通过分段线性化方法获得ZnO非线性电阻的I-V特性。最后,建立了一种基于实际10kV系统的模型,并通过ATP-EMTP进行比较和模拟不同的接地模式。结果表明,设计的ZnO非线性电阻参数可以抑制电弧接地过电压,并且所提出的接地模式是安全可靠的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有