INFLUENCE OF HARMONIC VOLTAGES ON SINGLE LINE TO GROUND FAULTS IN DISTRIBUTION NETWORKS WITH ISOLATED NEUTRAL OR RESONANT EARTHING

机译:用隔离中性或共振接地分布网络中单线对地面故障的谐波电压的影响

获取原文

摘要

Due to the relatively high content of the 5th and 7th harmonic that is accepted in the system voltage of MV distribution networks, the single line to ground fault (SLG) current in large distribution networks may be dominated by the harmonic SLG fault current contribution. The harmonic SLG fault currents can cause dangerous touch and step voltages if the impedance to earth is not sufficient low. The treatment of the neutral point plays an essential role, whether the distribution network consists of pure overhead lines (OH), pure underground cables (UC) or is a mixed system. The specific treatment of the neutral in distribution networks, isolated neutral and resonant earthing (RE), can for some configurations mitigate the harmonic SLG fault current content. This paper will therefore investigate the harmonic SLG fault current content with different treatment of the neutral point in OH and UC systems. The frequency dependency of the OH and UC parameters and of the soil resistivity in the earth return path are taken into account in the calculations, and the results are compared with measurements from a well defined distribution network to show and explain the influence of harmonic SLG fault currents. The measurements are carried out on a 10kV distribution network mainly supplying heavy fishing industry in Hirtshals, Denmark.
机译:由于在MV分配网络的系统电压中接受的第五和第7次谐波的相对较高的含量,大型分配网络中的单线到接地故障(SLG)电流可能由谐波SLG故障电流贡献主导。如果地球的阻抗不足,则谐波SLG故障电流可能会导致危险的触摸和阶跃电压。中性点的治疗起到了重要作用,分配网络是否由纯架空线(OH),纯地下电缆(UC)或是混合系统。对中性分配网络的具体治疗,隔离中性和谐振接地(RE),可以用于一些配置减轻了谐波SLG故障电流内容。因此,本文将研究谐波SLG故障电流含量与OH和UC系统中的中性点的不同处理。在计算中考虑了OH和UC参数和土壤电阻率的频率依赖性,并在计算中考虑了地球返回路径的电阻率,并将结果与​​来自定义的分销网络的测量进行了比较,以显示和解释谐波SLG故障的影响电流。测量在10kV分销网络上进行,主要在丹麦希茨海尔斯提供重型捕捞行业。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号