首页> 外文会议>International Conference and Exhibition on Electricity Distribution >INTERACTION BETWEEN POWER ELECTRONIC COMPONENTS AND DISTRIBUTION TRANSFORMERS - RISK EVALUATION AND MITIGATION TECHNIQUES
【24h】

INTERACTION BETWEEN POWER ELECTRONIC COMPONENTS AND DISTRIBUTION TRANSFORMERS - RISK EVALUATION AND MITIGATION TECHNIQUES

机译:电力电子元件与配电变压器之间的相互作用 - 风险评估和缓解技术

获取原文

摘要

The Geneva city utility SIG operates a large medium/low voltage distribution network with a high number of distribution transformers in place. Within the last approx. 4 years an unusual high number of transformer failed due to a premature aging. These units were all delivered between beginning of 1996 until mid 1999. Only sizes of 630 kVA and 1000 kVA were affected. Within other MV networks as well 400 kVA and 1250 kVA units failed, however a smaller number. Nondescript system failures, computer-/control system-/and process interruptions, apparatus and system destructions, explosions and fires were the reasons for 238 customer ordered measurements, network analyses and repairs in Germany, Austria, Switzerland, Italy and France throughout the years 2003 and 2004. Craftsmen's shops, doctor's cabinets, general stores, special repairshops, appartment houses in small and large cities, large offices, banking- and insurance buildings, large oil refineries, industries such as metal plastics manufacturing were affected internationally. At 157 cases systems and parts of them were destroyed. 7 cases resulted in building destructions following explosions and fire. Acc. to our knowledge the disturbances within the networks grew steadily from beginning of 1996 until the year 2000 and the increased exponentially. Within 229 cases the same cause could be determined. Concerned apparatus are capacitor bank with and without chokes, active filters, transformers, capacitors, process controls, computers, light controls, telephone switchboards, safety units (alarm and fire detectors) inverters and electronically controlled systems.
机译:日内瓦市Utility Sig运行一个大量的介质/低压配电网络,配有大量的分配变压器。在最后一个大约。 4年由于过早老化,不寻常的大量变压器失败。这些单位都在1996年初到1999年中期之间交付。只有630 kVA和100​​0 kVA的大小受到影响。在其他MV网络中,400 kVA和1250 kVA单元失败,但数字较小。非标签系统故障,计算机/控制系统/和过程中断,设备和系统破坏,爆炸和火灾是德国,奥地利,瑞士,意大利和法国在2003年德国,奥地利,瑞士,意大利和法国的238个客户订购测量,网络分析和维修的原因2004年,工匠的店铺,医生的橱柜,一般商店,特别的维修车,小城市,大型办公室,银行和保险建筑,大型石油炼油厂,金属塑料制造业等行业受到国际影响。在157例中,系统和部分地区被摧毁。 7例造成爆炸和火灾后建立破坏。 acc。我们知道网络内的干扰从1996年初直到2000年才稳步增长,并呈指数增长。在229例中,可以确定同样的原因。有关设备是电容器组,带有扼流圈,有源滤波器,变压器,电容器,过程控制,计算机,光控制,电话机,安全单元(报警和火灾检测器)逆变器和电子控制系统。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号