首页> 外文会议>International Conference and Exhibition on Electricity Distribution >Long term investigation of thermal behaviour of 110 kV underground transmission lines in the Belgrade area
【24h】

Long term investigation of thermal behaviour of 110 kV underground transmission lines in the Belgrade area

机译:贝尔格莱德地区110 kV地下传输线的热行为长期调查

获取原文

摘要

The paper presents the most important results of investigations of the thermal behaviour of 110 kV underground transmission lines. Special attention was paid to investigating the thermal behaviour of critical hot spots in the cable routes where, during characteristic annual weather periods, the soil surrounding the 110 kV underground transmission lines undergoes a long term process of drying. By measuring different hot spots, it has been determined that, due to the effect of drying out of the soil, they constantly operate at temperatures of the cable surface which are several tens of Celsius degrees above the value for normally humid soil. The paper describes the procedure for applying a special cable backfill material, developed and manufactured at the Nikola Tesla Institute for the thermal stabilisation and reduction of hot spot cable operating temperature, on specific hot spots of 110 kV underground transmission lines in Belgrade area. Continued investigations of the thermal behaviour have confirmed that the correct use of the backfill material is a necessary and sufficient means for removing the negative effects of soil drying on the increase of the operating temperature of 110 kV underground transmission lines. The results presented in this paper are an important contribution to the proof of the justification and necessity of defining and introducing in practice new procedures for the thermal stabilisation and reduction of operating temperature of existing, as well as of new underground transmission cable lines to be built.
机译:本文提出了110 kV地下传输线的热行为的研究结果。特别注意在电缆路线中调查关键热点的热行为,在特征年度天气期间,围绕110 kV地下传动线的土壤经过长期的干燥过程。通过测量不同的热点,已经确定,由于干燥土壤的效果,它们在电缆表面的温度下不断运行,这是几十个摄氏度高于正常潮湿的土壤的值。本文介绍了在Nikola Tesla研究所应用和制造的热点电缆工作温度的尼古拉Tesla研究所,在贝尔格莱德地区110 kV地下输电线路的特定热点上进行热稳定和减少的特殊电缆回填材料,在Nikola Tesla研究所的热稳定和减少。继续调查热行为证实,正确使用回填材料是一种必要的且充分的方法,用于去除土壤干燥对110kV地下传动线的工作温度的增加的负面影响。本文提出的结果是对定义和引入实践新程序的理由和必要性的重要贡献,以进行热稳定和现有工作温度的新程序,以及建造的新地下传输电缆线。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号