A great deal of research work on PD based cable insulation monitoring, diagnostics and localisation has been published in recent years on medium voltage (MV) cables. The work to be reported on extends PD detection and localisation into cross-bonded HV cable systems. The main challenge in PD monitoring of cross bonded HV cables lies in the interconnectedness of sheaths of the three phases, making it difficult to localise which of the three phases a PD signal has emanated from. A second challenge is the use of coaxial cables for connecting cable sheaths to cable link box for ease of installation and protection against moisture. The proposed paper addresses PD detection and localisation in cross-bonded HV cables. It presents experimental investigations into PD pulse coupling between the centre conductor and the cable sheath and the behaviour of PD pulse propagation in cross-bonded HV cables. It also proposes a model to describe the coupling effect in cross-bonding (CB) cable system for PD monitoring and localisation and demonstrates the effectiveness of the application of the model.
机译:近年来,有关中压(MV)电缆的基于PD的电缆绝缘监视,诊断和定位的大量研究工作已经发表。将要报告的工作将局放检测和定位扩展到交叉粘合的高压电缆系统中。 PD监测交叉结合的HV电缆的主要挑战在于三相护套的互连性,这使得很难确定PD信号来自三相中的哪一个。第二个挑战是使用同轴电缆将电缆护套连接到电缆接线盒,以简化安装并防潮。拟议论文探讨了交叉粘合高压电缆中的局放检测和定位。它提供了对中心导体和电缆护套之间的PD脉冲耦合以及PD脉冲在交叉粘结的HV电缆中传播行为的实验研究。它还提出了一个模型来描述交叉粘结(CB)电缆系统中用于PD监测和定位的耦合效应,并证明了该模型的应用有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号