This paper deals with a three-phase power system with hybrid transformer (HT). The HT contains a conventional three-phase transformer with electromagnetic coupling and AC/AC converter integrated with the secondary windings through an electric coupling. The HT uses a three-phase Yy connected transformer with additional secondary windings and three-phase voltage or current source matrix converter (VSMC or CSMC), which give possibility to changing the value and phase shifting of the output phase voltage. The paper gives a description of such power system with passive load, as well as the modelling and comparison of voltage transfer functions for both solutions of the HT. The steady state analysis results of power systems with simplified HT models are verified by means of the simulation and experimental test results obtained for the power system with HT of about6 kVA.
机译:本文涉及具有混合变压器(HT)的三相电力系统。 HT包含具有电磁耦合和AC / AC转换器的传统三相变压器,通过电耦合与次级绕组集成。 HT使用具有附加辅助绕组和三相电压或电流源矩阵转换器(VSMC或CSMC)的三相YY连接的变压器,这可以改变输出相电压的值和相移。本文介绍了具有被动负载的这种电力系统的描述,以及HT的两个解决方案的电压传递函数的建模和比较。通过对具有约6 kVA的电力系统获得的仿真和实验测试结果,验证了具有简化HT模型的电力系统的稳态分析结果。