首页> 外文会议>IEEE International Conference on Power Electronics and Drive Systems >Effectiveness of constant power factor control of mega-solar system for voltage regulation with long distribution line
【24h】

Effectiveness of constant power factor control of mega-solar system for voltage regulation with long distribution line

机译:大型太阳能系统的恒功率因数控制对长配电线路调压的有效性

获取原文

摘要

When a large-scale photovoltaic system, such as a mega-solar system, is connected to a distribution system, voltage variations on the distribution line may be caused by the output fluctuation of the photovoltaic system. This paper reports the result examined by numerical analysis and an experiment using a real system about mitigating the voltage variation by applying the reactive power control based on constant power factor control of the PCS in a large-scale photovoltaic system. It is investigated that the loss change on a distribution line influences the results of the reactive power control, especially when the large-scale photovoltaic system is interconnected with a long distance from a substation. This paper reveals that it is possible to mitigate a voltage variation sufficiently with the distance of about 5km from a substation to the interconnection point, and this method can be applied in many cases under the condition.
机译:当诸如兆太阳能系统的大规模光伏系统连接到配电系统时,配电线上的电压变化可能由光伏系统的输出波动引起。本文报告了通过数值分析和使用真实系统进行实验的结果,该系统通过在大型光伏系统中应用基于PCS恒定功率因数控制的无功功率控制来缓解电压变化。研究表明,配电线路上的损耗变化会影响无功功率控制的结果,尤其是在大型光伏系统与变电站的距离较长的情况下。本文揭示了可以从变电站到互连点的大约5km的距离充分缓解电压变化,并且该方法可以在这种情况下的许多情况下应用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号