首页> 外文会议>IEEE International Power Engineering and Optimization Conference >Correlation of furfural and moisture content with age of transformers
【24h】

Correlation of furfural and moisture content with age of transformers

机译:变压器年龄糠醛和水分含量的相关性

获取原文
获取外文期刊封面目录资料

摘要

This paper is aimed at analysis of correlation between age of 132/33kV and 33/11kV transformers with furfural concentration and carbon oxides content of oil. Also, the correlation of moisture content and relative humidity of oil/paper insulation system with furfural concentration of oil is investigated. The secondary data was obtained from the raw data of research studies which have been done in Malaysia on in-service power transformers. As a result, it is not only confirmed that furfural content in the oil was increased by increasing moisture content of the oil, but also there is a good correlation and significant relationship between furfural concentration of the oil and relative humidity of oil/paper insulation system. Also, descriptive statistics such as mean, standard deviation and normal distribution of furfural and moisture content per year of service of transformers described the level of evolution of moisture and furfural for these transformers at normal temperature.
机译:本文旨在分析132 / 33kV和33 / 11kV变压器的相关性,具有糠醛浓度和油的碳氧化物含量。此外,研究了具有糠醛浓度油的油/纸绝缘系统的水分含量和相对湿度的相关性。二次数据是从在马来西亚在服务在式电力变压器上完成的研究研究的原始数据获得。结果,不仅证实通过增加石油的水分含量而增加了油中油的糠醛含量,而且还存在良好的相关性和糠醛浓度与油/纸绝缘系统的相对湿度之间的关系。此外,诸如变压器服务的糠醛和水分含量的平均值,标准偏差和正常分布的描述性统计数据描述了在常温下对这些变压器的水分和糠醛的演变水平。