In this paper, a cooling control system based on Model Predictive Control is developed in order to reduce energy consumption of the facility equipment for the modular data center utilizing indirect fresh air, while considering the relationship between energy savings and temperature management of servers. Furthermore, the developed cooling control system is applied to the actual modular data center utilizing indirect fresh air, and its practical effectiveness is verified by conducting a demonstration experiment. To develop the proposed control system, a dynamic mathematical model for the actual modular data center is designed, and the proposed control system is mounted on an existing management server. The control system is able to operate without using a separate hardware controller. As a result, it is revealed that the proposed control system reduces facility's total power consumption by about 49% compared to a conventional system under condition where the supply air flow rate is 20°C.
机译:在本文中,开发了一种基于模型预测控制的冷却控制系统,以减少利用间接新鲜空气的模块化数据中心的设施设备的能量消耗,同时考虑到服务器的节能和温度管理之间的关系。此外,开发的冷却控制系统应用于利用间接新鲜空气的实际模块化数据中心,通过进行示范实验来验证其实际效果。为了开发所提出的控制系统,设计了实际模块化数据中心的动态数学模型,所提出的控制系统安装在现有管理服务器上。控制系统能够在不使用单独的硬件控制器的情况下进行操作。结果,揭示了所提出的控制系统与在供应空气流速为20°C的条件下的传统系统相比将设施的总功耗降低约49%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号