首页> 外文会议>IEEE International Symposium on Power Electronics for Distributed Generation Systems >A bilateral reactive power injection method for islanding detection of grid-connected converters in distributed generation units
【24h】

A bilateral reactive power injection method for islanding detection of grid-connected converters in distributed generation units

机译:一种双侧无功功率注入方法,用于分布式发电装置网格连接转换器的孤岛检测

获取原文

摘要

In this paper, a bilateral reactive power injection method is proposed for islanding detection of grid-connected converters in distributed generation units. The proposed method injects capacitive and inductive reactive power periodically with half of the grid frequency to perturb the frequency of point of common coupling (PCC). The magnitude of the injected reactive power is derived in order to remove the non-detection zone and the frequency of the injected reactive power is determined by considering parallel operation of the converters with no communication. In addition, the distortion of the currents by the proposed detection method is analyzed. The effectiveness of the proposed method is experimentally verified through the operation of two converters used for a 10kW battery energy storage system.
机译:本文提出了一种双侧无功功率注入方法,用于分布式发电单元中的网格连接转换器的孤岛检测。所提出的方法通过网格频率的一半将电容和电感无功功率注入扰动公共耦合点(PCC)的频率。通过考虑没有通信的转换器的并行操作来导出注入的无功功率的幅度,以去除非检测区,并且通过考虑转换器的并联操作来确定注入的无功功率的频率。另外,通过所提出的检测方法分析电流的失真。通过用于10kW电池储能系统的两个转换器的操作进行实验验证所提出的方法的有效性。

著录项