首页> 外文会议>IEEE International Symposium on Power Electronics for Distributed Generation Systems >Modeling the grid synchronization induced negative-resistor-like behavior in the output impedance of a three-phase photovoltaic inverter
【24h】

Modeling the grid synchronization induced negative-resistor-like behavior in the output impedance of a three-phase photovoltaic inverter

机译:在三相光伏逆变器的输出阻抗中建模电网同步诱导的负电阻式行为

获取原文

摘要

Photovoltaic power has to be converted from DC into AC in grid-connected applications. The conversion is done by using a single or three-phase inverter. Phase angle and frequency of the injected current and the grid voltage have to match to achieve unity power factor. This has been commonly accomplished by using a phase-locked-loop (PLL). The PLL has a tendency to make the output impedance of the inverter to appear as a negative resistor which can introduce harmonics in the grid current or even make the inverter-grid interface unstable. This paper presents a general small-signal model of a PV inverter in the synchronous reference frame which includes the PLL. Due to the negative resistance, the inverter can become unstable when the grid has high inductance. The derived small-signal model can be used to predict the exact conditions where the instability will take place by utilizing the impedance ratio and Nyquist stability criterion.
机译:光伏电源必须从DC转换为AC在网格连接的应用中。转换是通过使用单相或三相逆变器完成的。注入电流的相位角和频率,并且电网电压必须匹配以实现单位功率因数。这通常是通过使用锁相环(PLL)来实现的。 PLL具有使逆变器的输出阻抗出现为负电阻的趋势,这可以引入电网电流中的谐波,甚至使逆变器电网接口不稳定。本文介绍了在包括PLL的同步参考帧中的PV逆变器的一般小信号模型。由于负电阻,当电网具有高电感时,逆变器可能变得不稳定。衍生的小信号模型可用于预测通过利用阻抗比和奈奎斯特稳定性标准将发生不稳定性的确切条件。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号