首页> 外文会议>International Conference on Power Engineering, Energy and Electrical Drives >Transformers flux-linkage control in dynamic voltage restorer systems
【24h】

Transformers flux-linkage control in dynamic voltage restorer systems

机译:动态电压恢复器系统中的变压器磁链控制

获取原文

摘要

This work proposes to control the flux linkage of the dynamic voltage restorer (DVR) transformers through a proper correction in the voltage injections. The flux-linkages are calculated by means of the voltages in the transformers that are injected by the DVR. In case of exceeding the maximum flux saturation, a form factor is determined and the voltage injected is modified within a half cycle and the flux is appropriately shifted, which avoid the maximum flux-linkage excursion from being exceeded. Even so, if the opposite peak of the flux keep exceeding, the correction is performed with elimination of dc flux and simultaneously, one set the amplitude to the maximum value allowed. From this, the transformer does not enter into saturation mode which contributes to efficiency of the DVR. Simulation and experimental results are shown to prove the effectiveness of the method.
机译:这项工作建议通过对电压注入进行适当的校正来控制动态电压恢复(DVR)变压器的磁链。磁链是通过DVR注入的变压器中的电压来计算的。在超过最大磁通饱和度的情况下,确定形状因数,并在半个周期内修改注入的电压,并适当移动磁通,这可以避免超过最大磁通链偏移。即使这样,如果磁通量的相反峰值持续超过,则校正将在消除直流磁通量的同时进行,同时将幅度设置为允许的最大值。由此,变压器不会进入饱和模式,这会提高DVR的效率。仿真和实验结果证明了该方法的有效性。