首页> 外文会议>IEEE Photovoltaic Specialists Conference >Measured dc Arc-flash Risk in a Photovoltaic System
【24h】

Measured dc Arc-flash Risk in a Photovoltaic System

机译:测量光伏系统中的直流电弧闪光灯风险

获取原文

摘要

The deployment of high-power dc equipment are increasing, including solar photovoltaic (PV) plants, but very few studies have quantified dc arc-flash risks. Most dc arc-flash literature is based on the theory. More real-world testing is needed to compare theoretical calculations against real-world conditions to validate and improve predictions of hazards. This paper quantifies the risk from arc-flash in a commercially operating 1,000-kWdc ground-mounted PV-plant by measuring arc-current, arc-voltage, and incident energy and comparing results against existing models. The study reveals that none of the available models accurately predict real-world risk. It is also found that a PV source acts as a sustainable constant-current source during an arc-flash event.
机译:高功率直流设备的部署正在增加,包括太阳能光伏(PV)植物,但是很少的研究已经量化了DC Arc-Flash风险。大多数直流弧闪光文献都是基于理论。需要更真实的测试来比较理论计算对现实世界的条件来验证和改善危险预测。本文通过测量电弧电流,弧电压和入射能量,从商业运行的1,000-kWdc接地PV工厂中量化来自弧形闪光的风险,并将结果与​​现有模型进行比较。该研究表明,无可用的模型都没有准确地预测现实世界的风险。还发现PV源在ARC-Flash事件期间充当可持续恒流源。