首页> 外文会议>International refrigeration and air conditioning conference at Purdue >Effect of Microfins on Heat Rejection in Desuperheating, Condensation in Superheated Region and Two Phase Zone
【24h】

Effect of Microfins on Heat Rejection in Desuperheating, Condensation in Superheated Region and Two Phase Zone

机译:微翅片对过热区和两相区的过热降温,排热的影响

获取原文

摘要

Typical condenser design model simply divides the heat rejection process into de-superheating, two-phase, and subcooling. By neglecting condensation in presence of superheated vapor, error can be introduced. Experimental data on superheated CO_2 and R410A flow in horizontal microfin tubes of 6 mm inner diameter at reduced pressures from 0.55 to 0.95 are provided. Gradually increasing heat transfer coefficient, from when tube wall reaches saturation temperature, demonstrates the criteria of condensation occurrence and the proposed heat transfer model.
机译:典型的冷凝器设计模型将散热过程简单地分为过热,两相和过冷。通过在过热蒸气的存在下忽略冷凝,可以引入误差。提供了在0.55至0.95的减压下,内径为6 mm的水平微翅片管中过热CO_2和R410A流动的实验数据。从管壁达到饱和温度开始,逐渐增加的传热系数证明了凝结发生的标准和所提出的传热模型。